number can be set to any value between 0 and 255. To get INF and FUN for the
recorded binary signals, there are parameters on the disturbance recorder for each
input. The user must set these parameters to whatever he connects to the
corresponding input.
Refer to description of Main Function type set on the local HMI.
Recorded analog channels are sent with ASDU26 and ASDU31. One information
element in these ASDUs is called ACC, and it indicates the actual channel to be
processed. The channels on disturbance recorder are sent with an ACC as shown in
Table
.
Table 49:
Channels on disturbance recorder sent with a given ACC
DRA#-Input
ACC
IEC 60870-5-103 meaning
1
1
IL1
2
2
IL2
3
3
IL3
4
4
IN
5
5
UL1
6
6
UL2
7
7
UL3
8
8
UN
9
64
Private range
10
65
Private range
11
66
Private range
12
67
Private range
13
68
Private range
14
69
Private range
15
70
Private range
16
71
Private range
17
72
Private range
18
73
Private range
19
74
Private range
20
75
Private range
21
76
Private range
22
77
Private range
23
78
Private range
24
79
Private range
25
80
Private range
26
81
Private range
27
82
Private range
28
83
Private range
29
84
Private range
Table continues on next page
1MRK 511 394-UEN A
Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC
51
Communication protocol manual