INF
Description
TYP
GI
COT
82
Zone 5
2
N
1,7
83
Zone 6
2
N
1,7
84
Start general
2
Y
1,7,9
85
Breaker failure
2
N
1,7
86
Trip measuring system phase L1
2
N
1,7
87
Trip measuring system phase L2
2
N
1,7
88
Trip measuring system phase L3
2
N
1,7
89
Trip measuring system neutral N
2
N
1,7
90
Over current trip, stage low
2
N
1,7
91
Over current trip, stage high
2
N
1,7
92
Earth-fault trip, stage low
2
N
1,7
93
Earth-fault trip, stage high
2
N
1,7
4.1.6
IED status for IEC 60870-5-103 I103IED
4.1.6.1
Functionality
GUID-52AC7D0F-33C5-46FC-983E-5CB4B3517D88 v1
I103IED is a function block with defined IED functions in monitor direction. This
block uses parameter as
FunctionType
, and information number parameter is
defined for each input signal.
4.1.6.2
Function block
GUID-421D5C37-27A5-476A-A7D9-40E70AFDFDC8 v1
I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4
IEC10000292-2-en.vsd
IEC10000292 V2 EN-US
Figure 10:
I103IED function block
4.1.6.3
Signals
PID-3975-INPUTSIGNALS v5
Table 19:
I103IED Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
19_LEDRS
BOOLEAN
0
Information number 19, reset LEDs
21_TESTM
BOOLEAN
0
Information number 21, test mode is active
22_SETCH
BOOLEAN
0
Information number 22, setting changed
Table continues on next page
Section 4
1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
34
670 series 2.2 IEC
Communication protocol manual