5.3
Application layer
GUID-3D10FBA6-F562-4050-8A3E-3860ECCA9C0B v1
5.3.1
Transmission mode for application data
GUID-0020F6C3-3C0D-4A0F-8C00-4B3A71C36853 v1
Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
5.3.2
Common address of ASDU
GUID-4B6748D2-C329-4937-8C51-60EA28052A2A v2
Table 53:
Common address of ASDU
Supported
One COMMON ADDRESS OF ASDU (identical
with station address)
Yes
More than one COMMON ADDRESS OF ASDU
No
5.3.3
Selection of standard information numbers in monitor
direction
5.3.3.1
System functions in monitor direction
GUID-99E09728-48CD-4C67-97B5-73F564893E73 v2
Table 54:
System functions in monitor direction
INF
Semantics
Supported
0
End of general interrogation
Yes
0
Time synchronization
Yes
2
Reset FCB
Yes
3
Reset CU
Yes
4
Start/restart
Yes
5
Power on
Yes
5.3.3.2
Status indications in monitor direction
GUID-D1C20715-AC82-4FAB-B5AA-0E4A439C4129 v3
Table 55:
Status indications in monitor direction
INF
Semantics
Supported
16
Auto-recloser active
Yes
17
Teleprotection active
No
18
Protection active
No
19
LED reset
Yes
20
Monitor direction blocked
No
21
Test mode
Yes
22
Local parameter setting
Yes
Table continues on next page
Section 5
1MRK 511 394-UEN A
Interoperability
56
670 series 2.2 IEC
Communication protocol manual