Table 24:
I103SUPERV supported functions
INF
Description
TYP
GI
COT
32
Measurand supervision I
1
Y
1,7,9
33
Measurand supervision U
1
Y
1,7,9
37
I>>back-up operation
1
Y
1,7,9
38
VT fuse failure
1
Y
1,7,9
46
Group warning
1
Y
1,7,9
47
Group alarm
1
Y
1,7,9
4.1.8
Status for user defined signals for IEC 60870-5-103
I103USRDEF
4.1.8.1
Functionality
GUID-DADC9CE4-2E80-426C-A3B6-A8E8C7AC3CD4 v3
I103USRDEF is a function block with user defined input signals in monitor
direction. Each instance is associated with a Function Type (FUN) and each input
signal with an Information Number (INF). Additionally, all input signals may be
defined to use relative time and how to respond to a GI request.
The user is responsible for assigning a proper FUN value and proper INF values to
all connected inputs. See Settings for details.
4.1.8.2
Function block
GUID-B8312E77-514D-4117-BB31-B9907755580C v1
I103USRDEF
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
RT_START
IEC10000294-3-en.vsdx
IEC10000294 V3 EN-US
Figure 12:
I103USRDEF function block
1MRK 511 394-UEN A
Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC
37
Communication protocol manual