5.3.3.6
Auto-reclosure indications in monitor direction
GUID-88F9AFD6-6464-4DE1-AECB-595142BDCDB3 v2
Table 59:
Auto-reclosure indications in monitor direction
INF
Semantics
Supported
128
CB ‘on’ by AR
Yes
129
CB ‘on’ by long-time AR
No
130
AR blocked
Yes
5.3.3.7
Measurands in monitor direction
GUID-E3942660-0822-447E-BD4E-40D7C5088712 v3
Table 60:
Measurands in monitor direction
INF
Semantics
Supported
144
Measurand I
Yes
145
Measurands I, U
Yes
146
Measurands I, U, P, Q
Yes
147
Measurands I
N
, U
EN
Yes
148
Measurands I
L1,2,3,
U
L1,2,3,
P, Q, f
Yes
5.3.3.8
Generic functions in monitor direction
GUID-5F1B0569-3017-4642-BE64-19A2729DDE3D v2
Table 61:
Generic functions in monitor direction
INF
Semantics
Supported
240
Read headings of all defined groups
No
241
Read values or attributes of all entries of one
group
No
243
Read directory of a single entry
No
244
Read value or attribute of a single entry
No
245
End of general interrogation of generic data
No
249
Write entry with confirmation
No
250
Write entry with execution
No
251
Write entry aborted
No
5.3.4
Selection of standard information numbers in control
direction
5.3.4.1
System functions in control direction
GUID-2B4161BF-D245-4B25-9ED5-B185926E889F v2
Table 62:
System functions in control direction
INF
Semantics
Supported
0
Initiation of general interrogation
Yes
0
Time synchronization
Yes
1MRK 511 394-UEN A
Section 5
Interoperability
670 series 2.2 IEC
59
Communication protocol manual