Name
Type
Default
Description
93_IEF
BOOLEAN
0
Information number 93, earth-fault trip, stage high
ARINPROG
BOOLEAN
0
Autorecloser in progress (SMBRREC- INPROGR)
FLTLOC
BOOLEAN
0
Faultlocator faultlocation valid (LMBRFLO-
CALCMADE)
4.1.5.4
Settings
PID-6864-SETTINGS v1
Table 17:
I103FLTPROT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
128
Function type (1-255)
4.1.5.5
Supported information types
Function status fault protection for IEC 60870-5-103, I103FLTPROT
GUID-E9DF9410-F570-4F85-9063-C76D1D4A0668 v6
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each input signal.
Table 18:
I103FLTPROT supported functions
INF
Description
TYP
GI
COT
64
Start phase L1
2
Y
1,7,9
65
Start phase L2
2
Y
1,7,9
66
Start phase L3
2
Y
1,7,9
67
Start residual current IN
2
Y
1,7,9
68
Trip general
2
N
1,7
69
Trip phase L1
2
N
1,7
70
Trip phase L2
2
N
1,7
71
Trip phase L3
2
N
1,7
72
Back up trip I>>
2
N
1,7
73
Fault location in ohm
4
N
1,7
74
Forward/line
2
N
1,7
75
Reverse/busbar
2
N
1,7
76
Signal transmitted
2
N
1,7
77
Signal received
2
N
1,7
78
Zone 1
2
N
1,7
79
Zone 2
2
N
1,7
80
Zone 3
2
N
1,7
81
Zone 4
2
N
1,7
Table continues on next page
1MRK 511 394-UEN A
Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC
33
Communication protocol manual