4.1.8.5
Supported information types
Function status indications in monitor direction, user-defined,
I103USRDEF
M11874-137 v7
Function indication block in monitor direction with user-defined input signals.
Number of instances: 20
Function type is selected with parameter
FunctionType
.
Information number is required for each input signal.
Table 27:
I103USRDEF Information number default values
INF
Description
GI
TYP
COT
1
1)
Input signal 01
x/-
1/2
1,7,(9)
2*
Input signal 02
x/-
1/2
1,7,(9)
3*
Input signal 03
x/-
1/2
1,7,(9)
4*
Input signal 04
x/-
1/2
1,7,(9)
5*
Input signal 05
x/-
1/2
1,7,(9)
6*
Input signal 06
x/-
1/2
1,7,(9)
7*
Input signal 07
x/-
1/2
1,7,(9)
8*
Input signal 08
x/-
1/2
1,7,(9)
1) * User defined information number
4.2
Commands in control direction
M11874-27 v1
4.2.1
Function commands for IEC 60870-5-103 I103CMD
4.2.1.1
Functionality
GUID-973929FE-292B-42A5-ACF9-BC95E2B16AE1 v2
I103CMD is a command function block in control direction with pre-defined
output signals. The signals are in steady state, not pulsed, and stored in the IED in
case of restart.
4.2.1.2
Function block
GUID-C0680812-C488-4546-AA65-F590955DBF0C v1
IEC10000282-1-en.vsd
I103CMD
BLOCK
16-AR
17-DIFF
18-PROT
IEC10000282 V1 EN-US
Figure 13:
I103CMD function block
Section 4
1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
40
670 series 2.2 IEC
Communication protocol manual