Table 39:
I103USRCMD supported indications
INF
1)
Description
1
Output signal 01
2
Output signal 02
3
Output signal 03
4
Output signal 04
5
Output signal 05
6
Output signal 06
7
Output signal 07
8
Output signal 08
1) User defined information number
4.2.4
Function commands generic for IEC 60870-5-103
I103GENCMD
4.2.4.1
Functionality
GUID-729E9AFD-0468-4BBD-B54A-A6CDCC68A9B2 v3
I103GENCMD is used for transmitting generic commands over IEC 60870-5-103.
The function has two outputs signals CMD_OFF and CMD_ON that can be used to
implement double-point command schemes.
The I103GENCMD component can be configured as either 2 pulsed ON/OFF or 2
steady ON/OFF outputs. The ON output is pulsed with a command with value 2,
while the OFF output is pulsed with a command value 1. If in steady mode is ON
asserted and OFF deasserted with command 2 and vice versa with command 1.
Steady mode is selected by setting PulseLength=0. The I103GENCMD is retained,
and a command in steady mode will be reissued on restart.
4.2.4.2
Function block
GUID-6EC8453E-0D00-4720-95A6-156C41CA46BB v1
IEC10000285-1-en.vsd
I103GENCMD
BLOCK
^CMD_OFF
^CMD_ON
IEC10000285 V1 EN-US
Figure 16:
I103GENCMD function block
4.2.4.3
Signals
PID-3970-INPUTSIGNALS v5
Table 40:
I103GENCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
1MRK 511 394-UEN A
Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC
45
Communication protocol manual