Commissioning
SA/S | 2CDC 505 056 D0208 99
Change Threshold 1 over bus
Options:
no
yes
This parameter defines whether threshold value 1 can or cannot be changed via the bus.
•
yes: Communication object
Threshold value 1
can be changed via the bus. This can be a 1 or 2 byte
communication object depending on the parameterization of the threshold value input.
•
no
: The communication object
Threshold value 1
cannot be changed via the bus.
With the parameter
Overwrite scene, preset and threshold value 1 with download
in parameter window
A:
General
, it is possible during a download to not overwrite the threshold values set via the bus and thus
to protect them.
Threshold value 1 [0...255]
The value range is dependent on the selection made in the parameter
Data type of object "Threshold
input"
.
1 byte [0…255]:
Options:
0…80…255
2 byte [0…65,535]:
Options:
0…20,000…65,535
Threshold value 2 [0...255]
The value range is dependent on the selection made in the parameter
Data type of object "Threshold
input"
.
1 byte [0…255]:
Options:
0…160…255
2 byte [0…65,535]:
Options:
0…40,000…65,535
Threshold values define hysteresis
Options:
no
yes
This parameter defines whether Threshold values 1 and 2 should be interpreted as hysteresis limits.
The hysteresis can reduce continuous threshold value messages if the input value fluctuates around one
of the threshold values.
For further information see:
Threshold function
, p. 159
With option
yes
, the following parameters appear: