Commissioning
88 2CDC 505 056 D0208 | SA/S
Reaction on preset 2 (telegr. value 1)
Options:
no reaction
ON
OFF
This parameter determines the contact position that the output assumes when preset 2 is recalled, i.e.,
communication object
Recall Preset 1/2
receives a telegram with the value 1.
At the same time, on the first call up of preset 2, the state of the output is saved so that the value before
preset 2 can be restored if the setting is changed accordingly.
Preset can be set via the bus
Options:
no
yes
This parameter enables the communication object
Set preset 1/2
. It is thus possible to store the current
contact position as the new preset value.
Telegram value 0 saves preset 1, whereas telegram value 1 saves preset 2.
If the option
no reaction
,
restore old value before preset 2
or
restore parameterized value of preset 2
has
been selected in parameter
Reaction on preset 1 (telegr. value 0)
, no new communication object value is
saved.
Using the parameter
Overwrite scene, preset and threshold value 1 with download
in parameter window
A:
General
, it is possible not to overwrite the scene values set via the bus during a download and thus to
protect them.
If a mains voltage failure occurs the stored preset values are lost. They are overwritten by the
parameterized default values.