![ABB i-bus SA/S 12.10.2.1 Скачать руководство пользователя страница 105](http://html.mh-extra.com/html/abb/i-bus-sa-s-12-10-2-1/i-bus-sa-s-12-10-2-1_product-manual_3077105.webp)
ABB i-bus
KNX
Commissioning
108 2CDC 505 056 D0208 | SA/S
•
send "1" when crossing lower
: Should current threshold value 1 be undershot, communication
object
Status Current-Threshold 1
sends the value 1. An overshoot sets the value to 0 but no
telegram is sent.
•
send "0" at crossing over – "1" at crossing lower
: Should current threshold value 1 be overshot,
communication object
Status Current-Threshold 1
sends the value 0, or if the threshold is
undershot, 1.
•
send "1" at crossing over – "0" at crossing lower
: Should current threshold value 1 be overshot,
communication object
Status Current-Threshold 1
sends the value 1, or if the threshold is
undershot, 0.
The status is sent after the evaluation delay at the earliest and only if the status has changed.
Enable current threshold 2
Options:
no
yes
This parameter enables the second current threshold value and its associated communication object
Status Current-Threshold 2
. The same evaluation delay, scaling, and evaluation properties as for
Threshold 1 apply.
•
yes
: The following parameter appears:
Current threshold 2 in mA
(scaled in 10mA or 100mA)
Value of hysteresis current
threshold 2
Current threshold 2 +/- hysteresis
The setting options for this parameter are the same as for current threshold value 1. Parameter
descriptions can be found earlier in this section.
Only for sinusoidal current the
current value is the rms value
see technical data
Содержание i-bus SA/S 12.10.2.1
Страница 1: ...ABB i bus KNX SA S Switch Actuators Product Manual ...
Страница 137: ......