![ABB i-bus SA/S 12.10.2.1 Скачать руководство пользователя страница 130](http://html.mh-extra.com/html/abb/i-bus-sa-s-12-10-2-1/i-bus-sa-s-12-10-2-1_product-manual_3077130.webp)
ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 133
3.2.6
Communications objects, operating mode Heating Actuator
3.2.6.1
Communication objects, General
No.
Function
Object name
Data type
Flags
0
In Operation
General
EIS 1, 1 bit
DPT 1.002
C, R, T
To regularly monitor the presence of the Switch Actuator on the ABB i-bus
®,
a monitoring telegram can be sent cyclically via
the bus.
This communication object is always enabled.
Telegram value:
1 = system in operation
0 = send inactive
1
Safety Priority 1
General
EIS 1, 1 bit
DPT 1.005
C, W, U
This communication object is enabled if the option
enabled by object value "0"
or
enabled by object value "1"
is selected for
parameter
Function Safety Priority 1
in the
General
parameter window.
The Switch Actuator can receive a 1 bit telegram via this communication object, which another KNX device, e.g. diagnostics
module or wind sensor, sends cyclically. On receipt of the telegram, the communication capability of the bus or the sensor
(signaling device) can be monitored. If the Switch Actuator does not receive a telegram on the communication object
Safety
Priority 1
within a certain time (value can be parameterized), a fault is assumed and a response, as parameterized in
parameter window
A:
Safety
, is implemented. The output of the Switch Actuator goes into a safety state and does not
process any telegrams. Only after communication object
Safety Priority 1
receives a 1 or 0 again (depending on the
parameterization) will incoming telegrams be processed again and the contact position changed.
The monitoring period can be adjusted in the parameter
Monitoring time in seconds
.
Safety Priority 1 is also triggered if a telegram with the parameterizable trigger value is received.