ABB i-bus
KNX
Planning and application
148 2CDC 505 056 D0208 | SA/S
Example
If both communication objects
Logical connection x
are activated, a telegram received via
communication object
Switch
is connected to them. The result of this action serves as the input signal
for the Time function. If this is not disabled, a corresponding switch signal is generated, e.g. delay or
flashing. Before the switch telegram reaches the relay, communication objects
Safety Priority x
and
Forced operation
are checked and undertaken, if required, as a priority. Subsequently, the switching
action is only dependent on the state of the bus voltage. The relay is switched if a switching action
allows it.
4.2.2
Time function
The Time function can be enabled (value 0) and disabled (value 1) via the bus (1 bit communication object
Disable time function
). The output operates without a delay as long as the
Time
function is disabled.
Various functions can be undertaken using the Time function:
•
Staircase lighting
•
ON/OFF delay
•
Flashing
4.2.2.1
Staircase lighting
After the staircase lighting time T
ON
has elapsed, the output switches off automatically. For every telegram
with the value 1 the time restarts (
retrigger function
), if the parameter
Extending staircase lighting by
multiple operation ("pumping up")
in
Parameter window
A: Time
, p. 76 is set to
no, no pump up possible
.
This corresponds with the basic response of the Staircase lighting function as long as a warning is not
parameterized.