ABB i-bus
KNX
Commissioning
138 2CDC 505 056 D0208 | SA/S
No.
Function
Object name
Data type
Flags
15
Status heating
Output A
EIS 1, 1 bit
DPT 1.001
C, T
This communication object is visible if control of the heating actuator is implemented via a 1 bit communication object,
e.g. within a continuous control, and feedback of the control value is also parameterized with a 1 bit value.
The current 1 bit control value of the output is sent via this communication object when there is a change.
With selection of the option
0% = "0" otherwise "1"
, the following applies:
Telegram value:
1 = control value is not equal to 0 %
0 = control value is equal to 0 %
Telegram value:
1 = control value is equal to 0 %
0 = control value is not equal to 0 %
16…
24
Not assigned
25
Contact monitoring
Output A
EIS 1, 1 bit
DPT 1.002
C, T
This communication object is enabled if the
yes
option is selected for parameter
Enable function "current detection"
in the
A:
Function
parameter window.
The communication object value shows the contact state when the contact is open.
Should a current flow be detected on a contact opened via KNX, contact welding or manual switch on has occurred (contact
fault). Evaluation of whether a current is flowing occurs about one second after a contact is opened. Current will definitely be
detected if a measurable current (about 20 mA) is flowing. A KNX switch operation is required for evaluation to work properly.
Telegram value
1 = contact error
0 = no current is flowing
26
Current Value
Output A
EIS 10, 2 byte
DPT 7.012
C, R, T
This communication object is enabled if the
yes
option has been selected for parameter
Enable function "current detection"
in the
A: Function
parameter window and the 2 byte datapoint type has been selected in the
A: Current Detection
parameter
window.
The presently detected current is transferred via KNX; 1 digit corresponds to 1
mA.
For further information see:
Current detection specifications
, p. 44
26
Current Value
Output A
EIS 9, 4 byte
DPT 14.019
C, R, T
This communication object is enabled if the
yes
option has been selected for parameter
Enable function "current detection"
in the
A: Function
parameter window and the 4 byte datapoint type has been selected in the
A: Current Detection
parameter
window.
The current value is transferred via KNX as a mA value.
For further information see:
Current detection specifications
, p. 44