ABB i-bus
KNX
Planning and application
168 2CDC 505 056 D0208 | SA/S
Reaction on:
Bus voltage recovery
Download
ETS bus reset
Operating mode Switch
Actuator
Switch object
Parameterizable
1)
(Parameter window
X: General
)
Unchanged. Evaluation only after
a new event has been received.
As for download
Time function
Enable can be parameterized (parameter
window
X: Function
), timer out of operation.
Unchanged, timer out of
operation.
As for download
Staircase lighting
In the
X: Function
parameter window you can
set whether or not the Time function is
disabled after bus voltage recovery.
Otherwise unchanged. Changes only after a
new event has been received.
The staircase lighting time as changed via
the bus is lost, and replaced by the time
which is parameterized in ETS.
Unchanged. Changes only after
an event has been received.
e.g. the staircase lighting remains
on until it is started again or
switched off
As for download
Time delays
Unchanged. Changes only after an event has
been received.
Unchanged. Changes only after
an event has been received.
As for download
Flashing
Unchanged. Changes only after an event has
been received.
Unchanged. Changes only after
an event has been received.
As for download
Permanent ON
Parameterizable (parameter window
X: Time
)
Unchanged
As for download
Preset/scenes
The preset and scene values stored in the
SA/S are restored if the parameter for
overwrite at download has been set to
yes
.
When set to
no
, the values stored via KNX
are retained.
Overwriting scene and preset
values can be parameterized
(parameter window
X: General
)
The stored preset and
scene values in the SA/S
are restored.
Logic
(Communication object Logical
connection x)
Can be parameterized (parameter window
X: Logic
). Only evaluated after next event.
Only evaluated after next event.
As for download
Threshold (communication
object Threshold input)
Can be parameterized (parameter window
X: Threshold
). Only evaluated after next
event.
Only evaluated after next event.
As for download
1)
Before the very first download (device fresh from the factory), the value before bus voltage failure is not defined.
For this reason, the communication object
Switch
is written with 0 and the contact is opened, even though the default setting is
not write
.