HVC 450 kW E-Bus Charger Installation Guide
Revision: 1.2
COMPANY CONFIDENTIAL
Date released: 16-08-2018
Page
46
of
128
NOTICE
To already fixed the sidewalk around the pole, there can be placed border
collar around the top of the foundation to have free access of the bolts.
4.4. Cabling
4.4.1. About cabling
There are various cabling solutions, depending on the installation situation and the cable types
used.
When the cables are routed below ground, use cables that are suitable for
underground installation.
The identity and/or function must be marked on every 78.74 Inch of the cables and on
both ends.
NOTICE
ABB recommends the use of crimped lugs for cable connections to Power
Cabinet and Charge Post. Mechanical lugs can be used at the discretion
of the installer and will be separately provided.
CAUTION
ABB is not responsible for damage caused to the Charger system due to
the use of mechanical lugs, and is not covered by the warranty.