14
TR A N S FOR M E R BUS H I NG S T Y PE G S B 8 0 0
I N S TA L L AT I O N A N D M A I N T EN A N C E G U I D E
2.10.1 Installation of standard end-shield
Alternative 1: Mounting the standard end-shield on the
bottom contact adapter. Fig. 17.
1. Mount the socket screws with springs to the bottom
contact adapter.
2. Connect the cable lugs to the bottom contact.
Tightening torque 68 ± 6 Nm.
3. Push the end-shield gently against the bottom contact
adapter, guiding the socket screws through the key
holes.
4. While applying force, turn the end-shield clockwise
approximately 20° and then release when in locked
position.
Alternative 2: Mounting the standard end-shield on the
bottom contact. Fig. 18.
1. Mount the socket screws with springs to the bottom
contact.
2. Connect the cable lugs to the bottom contact.
Tightening torque 68 ± 6 Nm.
3. Push the end-shield gently against the bottom contact,
guiding the socket screws through the key holes.
4. While applying force, turn the end-shield clockwise
approximately 20° and then release when in locked
position.
Socket
screw
with
spring
Socket screw
with spring
—
17 Alternative 1: Mounting the standard end-shield on the bottom contact adapter.
—
18 Alternative 2: Mounting the standard end-shield on the bottom contact.