TR A N S FOR M E R BUS H I NG S T YPE G S B 8 0 0
I N S TA L L AT I O N A N D M A I N T EN A N C E G U I D E
13
Lo
w
er dra
w
-r
od
Upper dra
w
-r
od
2.10 Draw-rod system
The draw-rod system can be divided level with the mounting
flange. Fig. 16 shows the draw-rod system and the joints
that are locked at delivery.
The additional joint at flange level must be locked with
locking fluid (Loctite 242 and activator Loctite T747) on site.
The threads must be degreased before applying the locking
fluid.
Supporting the lower draw-rod during transportation
The lower draw-rod can be used for supporting the bottom
contact and the cables in the transformer tank during
transport of the transformer/reactor, as shown in Fig. 15.
Mounting of the draw-rod must be performed
according to the described procedures.
Additional joint
on request
Standard joint,
locked at delivery
Standard joint at
flange level, lower
thread unlocked at
delivery
Locked with
locking fluid at
delivery
Lower thread
unlocked at
delivery
Threaded sleeve
M10 x 30 mm
Transport
cover
Standard
end-shield
Transformer
/reactor
Cables
—
15 Lower draw-rod support during transportation.
—
16 Joints of the draw-rod system.