11
→
9 EVENT LOG TO LCD
–
Allows the user to view the history of previous events.
Upto 99 events with the time and date can be stored.
The LCD will display the last/most recent event - given event no.1. New events are always given event no.1.
Events are given numbers in ascending order to when they occurred from 1-most recent to 99-the oldest event.
Fir 10:26 30/10 2003
FIRE-Panel 1 zn 8
KITCHEN
1of99 Up Dn Exit
Button 3-
NOT available
Text above button 3 is the event number.
Button 4- Up
moves up event log to
more recent events.
Button 5- Dn
moves down event log to
older events.
Button 6- exit
returns to menu system.
Event types are as follows:-
- Zone
X
in fire
- Fire activation in zone number 1 to 16
- Fire Panel
Y
Zn
X
- Another fire panel 1 to 32 (
Y
), to which this is networked to, has a Fire
activation in zone 1 to 16 (
X
).
- Zone
X
Detectr Fire
- An Alarm Sense detector on zone 1 to 16 has a fire activation.
- Zone
X
Callpnt Fire
- An Alarm Sense Call Point on zone 1 to 16 has a fire activation.
- Alarms Silenced
- Activated alarms have been switched off.
- Alarms Resounded
- Alarms that have been Silenced, have been re-activated.
- Zn
X
Missng/oper/Eol
- Zone 1 to 16 either Detector is missing, or Zone wiring is open circuit or End of
Line device is missing.
- Zn
X
Short Circuit
- Zone 1 to 16 short circuit.
- Zn
X
Fire Cleared
- A fire activation in an Un-Latching zone number 1 to 16 is cleared.
- Zone
X
Det Missing
- An Alarm Sense detector is removed on zone 1 to 16.
- Panel Evacuated
- Evacuate option has been selected.
- Pnl
X
AL
Y
Short Circuit
- Another fire panel 1 to 32 (
X
), to which this is networked to, has an fault on
Alarm Line 1 to 4 (
Y
).
- Pnl
X
EoL AL
Y
msng
- Another fire panel 1 to 32, to which this is networked to, is either Open Circuit
or the End of Line EoL device is missing on Alarm Line 1 to 4.
- Fault on Panel
X
- Another fire panel 1 to 32, to which this is networked to, is in a fault condition.
This is qualified by a description of the fault that has occurred.
- NetTimeout @ addr
X
- Panel 1 to 32 (
X
) to which this fire panel is networked to is not responding.
- Micro CRC Fault
- The fire control panel software has become corrupted.
- Dual Address
- Another panel with same address 1 to 32 has been detected.
- Mains Failed
- 230VAC input is disconnected.
- Battery Missing
- The standby battery is disconnected or faulty.
- Aux 12v Fault
- 12v Auxiliary output from the fire panel has failed.
- Aux 24v Fault
- 24v Auxiliary output from the fire panel has failed.
- Temp Sensor Fail
- Temperature sensor used for battery charging is disconnected or short circuit.
- Earth Fault
- A fault to Earth on the system wiring has been detected.
- Watchdog Reset
- Fire panel has been re-started by the supervision circuitry.
- Panel Reset
- The fire panel has been reset to its quiescent condition – No fires, faults etc.
- Zn
X
Walktested
- Zone 1 to 16 of the fire panel has been fire tested.
- Engnr Panel Default
- Panel has been restored to factory settings.
→
10 OVERRIDE DELAYS
–
In a fire condition, if there is a delay before the alarms are sounded, this
function will cause the alarms to ring immediately.
If there is a delay operating, the ‘DELAY ENABLED’ LED will be illuminated. This will be switched off when the
Over ride Delays has been selected.
→
11 EVACUATE
–
This will cause the main fire alarm sounders to ring. The internal buzzer in the panel will
be made to sound and the ‘GENERAL FIRE’ LED will be illuminated.
→
12 EXIT
–
Returns out of menu system back to fire alarm panel.