42
→
29 DATA PC>PANEL
–
This function allows text and ringing patterns to be sent to the Eurofire EN54 from a PC.
In order to do this the following is required:-
-
Text and ringing patterns created in a file.
-
A PC with ‘HyperTerminal’ installed on it
-
An Emergi-Lite Converter Cable.
1) Firstly set up the PC to Panel connection as shown above in ‘EVENT LOG TO PC’.
2) Select
option
→
29 DATA PC>PANEL –
from the menu system of the Eurofire EN54. The Eurofire EN54
panel is now ready to received data from the PC, the LCD will show:-
Get Data From PC
Use Hyperterminal
4800-n-8-1 Send Txt
Echos to PC exit
The panel is ready to receive data from
the PC
button 6 exit -
Should you not want to
get data from the PC. This will return
you to the menu system.
3) Start ‘HyperTerminal’ with the following settings:-
Bits Per Sec = 4800,
Data Bits = 8,
Parity = None,
Stop Bits = 1,
Flow Control = None.
4) In ‘HyperTerminal’, from the ‘TRANSFER’ tab select the ‘Send file…’ option.
Then select the file, which contains the text and ringing patterns, and then press ‘send’
→
30 DATA PANEL>PC
–
Sends text and ringing patterns of the Eurofire EN54 to a PC.
The following is required:-
-
A PC with ‘HyperTerminal’ installed
-
An Emergi-Lite Converter Cable.
1) Set up PC to Panel connection as shown above in ‘EVENT LOG TO PC’.
2) Start ‘HyperTerminal’ with the following settings:-
Bits Per Sec = 4800,
Data Bits = 8,
Parity = None,
Stop Bits = 1,
Flow Control = None.
3) In ‘HyperTerminal’, select ‘TRANSFER’ tab and then ‘Capture Text’, choose a name and location where the
file is to be saved.
4) From the menu system of the Eurofire EN54, select option
→
30 DATA PANEL>PC
. Text and ringing
patterns will now be sent to the PC.
Sending data to PC
The panel is sending text and ringing
patterns to the PC.
→
31 CLEAR EVENT LOG
–
This function clears all events from the event long.
→
32 DEFAULT PANEL
–
This function restores the panel to factory settings.
The default is done in stages so that specific settings can remain unaltered if required.
→
33 CHANGE USER CODE
–
This function allows the user code to be changed.
The user code can only be changed to one containing a combination of 3, 4, 5, and 6 only.
The user password is only changed if the new password is twice typed in the same.