To set up a network:-
1) Ensure that the wiring of the network is correct, and the network terminators are correctly placed for the
installation. 2 terminators must be present in the networked system – they must be placed on panels or repeaters
that are at the two furthest points on the network. Failure to do this could result in the network operating
incorrectly or not operating at all.
2) Each Panel/Repeater to be networked, must have its network address, method of networking (net mode) and the
network speed set. If the net speed or method of networking (net mode) is set different to other devices on the
network, the network will NOT operate.
Ensure that each panel/repeater is given a different network addresses. Failure to do so will cause faults to occur
with the networking.
3) After all panels/repeaters have been addressed, go to each Panel and Repeater, and through the networking menu
connect them to one another. This will ensure that all devices are networked to each other.
4) The network should now be setup. On each panel, if required, you should create ringing patterns – when a fire is
detected on the panel, it will send all alarm ringing patterns that have been given a NetAddress to the other panels
that are networked to it.
The pattern is created like normal but you give the NetAdd address of the panel to where the pattern is to go to.
A new pattern, one for each network address to where the pattern is to be activated will have to be created. This
is done through options 16 Edit Pattern and 17 Assign Zn Pttrns.