31
→
18 ASSIGN CLASS PAT
–
This assigns Class Change to a pattern. When Class Change is activated then the patterns assigned to it will operate.
Set Class Patterns
Pattern number 0
ACTIVE
toggle Pup Pdwn exit
Shows that when class change is
activated Pattern 0 will Activate.
Button 3 –
toggle
will activate and
deactivate the pattern.
Button 4 –
Pup
moves to next pattern.
Button 5 –
Pdwn
moves to previous
pattern.
Button 6 –
exit
returns back to menu
system saving the settings at same time.
By default Pattern 0 is assigned to Class Change (Pattern 0 is AL1,2,3 &4 activated continuously)
→
19 ASSIGN BOMB PAT
–
Assigns pattern to Bomb Alert in the same way as Class Change.
→
20 ASSIGN SPECL PAT
–
Assigns pattern to the Programmable Input in the same way as Class Change.
→
21 ASSIGN EVAC PAT
–
Assigns pattern to Evacuate in the same way as Class Change.
→
22 TEST PATTERN
–
Allows you to operate the pattern without having to put the panel into a fire condition. This allows you to verify that
a pattern is correct before it is assigned to a condition.
Ptrn 0 – Test?
Test Up Dwn exit
Allows a pattern to be operated before
assigning it to a condition.
Button 3 –
Test
causes the pattern to
operate.
Button 4 –
Up
next pattern.
Button 5 –
Dwn
previous pattern.
Button 6 –
exit
returns back to menu.
→
23 SET ZONE CONFIG
–
Sets zone configuration ie. Conventional, Two Wire, Latching/Unlatching etc.
Zones can be individually configured to be either conventional or Two Wire (Alarm Sense.) The control panel can
therefore be configured as either:-
•
All zones are Conventional only.
•
All zones are Alarm Sense (Two Wire) only.
•
Or a mixture of Conventional and Alarm Sense zones, i.e some zones are configured as
Conventional and some configured as Two Wire (Alarm Sense.)
When setting a zone as conventional, the options available are:-
•
Latching or Unlatching zone.
•
470Ohm or Short Circuit fire detection.
When a zone is set as conventional, these should also be set as required for the installation.
When setting a zone as Two Wire (Alarm Sense), option available for the zone setting is:-
•
Latching or Unlatching zone.
This should be set as required for the installation.
The Eurofire panels are supplied as either:-
•
Conventional only (470Ohm and Latching fire condition) – FEUN.
or
•
Alarm Sense (Two Wire) only (Latching fire condition) - FEWN.