Engineers Menu Functions
→
14 WLKTST ALL ZONES
–
Enables the user to test the fire detectors and call points on all zones of the
fire alarm system.
Walktesting
16 of 16 zones
Alarms to sound
sndr exit
Button 3- sndr
selects whether or not to
activate the alarms when a device is
tested.
Button 6- exit
returns to menu system.
Selecting Walktest all zones, will illuminate the ‘DISABLED’, ‘TEST’ and all Zone Fault LEDs:-
When a callpoint or detector is activated, the fire LED of the zone tested will be illuminated. If alarm to sound is
selected, the sounders will ring for 2seconds. Thus the operation of each detector and callpoint on the fire system can
be verified.
Note,
The panel will automatically exit from Walktest if there is no activation for 15minutes.
During walktest, devices connected to the panel via the auxiliary contacts or devices on the network will not
be triggered.
→
15 AUXILIARY TEST
–
Switches the Auxiliary contacts over .
To end testing auxiliaries, press
‘END’
– This will return you to the menu system.
→
16 EDIT PATTERN
–
The Eurofire panel uses patterns to switch On/Off devices (alarms, zone sounders and auxiliary relays.) Patterns
must be created and then assigned to zones, otherwise, the devices will not operate as required. The Eurofire has a
total of 32 patterns available. Each zone can be allocated a number of patterns.
The Eurofire panel has been designed to allow flexible programming of the alarm and auxiliary relays. Each of the
alarm and auxiliary relays can be programmed to be continuous or pulsed with or without an initial turn-on delay.
They can be programmed to operate for a period of upto 3600 seconds or until reset. Each Zone can be allocated a
number of patterns. For example, pattern 1 could be programmed to activate alarm relay 1 and zone 3 is allocated to
this pattern. Therefore when zone 3 is triggered the sounders on alarm circuit 1 will operate. Likewise Pattern 2
could be programmed to trigger alarm relay 4. This pattern could then be allocated to zones 3 to 9. Thus if a zone,
between Z3 and 9 were to be activated then alarm relay 4 would be triggered. A pattern can be used/assigned to more
than 1 zone. E.g. pattern 0 can be used/assigned to zone1, zone3 and zone5.
Patterns can be assigned to any zone or combination of zones as required. Thus the fire systems alarm response can be
programmed to the individual needs of any particular installation.