33
To alter a Conventional zone in to a TwoWire (Alarm Sense) zone, for example Zone 2:-
-
Remove Link J11 – This will ensure that the correct voltage is put on to the zone 2.
-
Through option 23.
→
23 SET ZONE CONFIG,
Set the configuration of Zone 2 to
TwoWire
.
-
If sounders have been installed onto the zone, alarm patterns will have to be created so that the
sounders activate in a fire condition:-
-
Through option 16 -
→
16 EDIT PATTERN
– Create a pattern that will activate zone 2 sounders.
Pattern 4
Zone 2 Sounder
→
Pattern Details
Item Edit Exit
Ensure that Zone 2 Sounder is selected in
the pattern.
Then edit the pattern details so that the
sounder will operate as required, for
example, sound until reset:-
See below:-
NetAdd
→
0
Delay 0
Pulse 0 On1 Off0
Pattern time CONT
Item Up Dwn Back
NetAdd 0 – To ring locally on the panel.
Delay = 0 Seconds.
Pulse time = 0 Seconds.
(alarms will not be pulsed)
Durn = CONT (sounder will be activated
until panel is reset or silenced)
On time = 0 sec Off time = 0sec.
-
Through option 17 -
→
17 ASSIGN ZN PTTRNS
– Assign this pattern to all zones.
The sounder will now activate when any zone goes into fire.
To alter a zone to Conventional from Two wire – for example change zone 2 to Conventional from TwoWire.
-
Insert link into J11 – This will put the correct voltage on to zone 2 for conventional detectors.
-
Through option 23.
→
23 SET ZONE CONFIG,
Set the configuration of Zone 2 to
Conventional
.
-
Through option 16 -
→
16 EDIT PATTERN
and option 17
→
17 ASSIGN ZN PTTRNS
– Check
that the patterns for zone 2 are still correct and valid – They may require modifying or removing.
→
24 ENTER ZONE TEXT
–
This function allows text to be entered against each of the available zones. The text is one line of 20 characters
which is displayed on the LCD when there is a fire condition on the zone.
Edit Zone 1 Text?
Zone 1 TEXT
Edit Up Dwn Exit
Button 3 –
Edit
will allow you to edit
the text shown on line 2.
Button 4 –
Up
moves to next zone text
Button 5 –
Dwn
moves to previous
zone text.
Button 6 –
exit
returns back to menu
system saving the changes.
When
button 3 Edit
is selected, will bring up the editing menu:-
Editing Zone 1 Text?
Zone 1 TEXT
^
←
Up Dn
→
Button 3 –
←
moves cursor (^) to
previous character.
Button 4 –
Up
edits character upwards.
Button 5 –
Dn
edits character
downwards.
Button 6 –
→
moves cursor (^) to next
character.
When editing the last character (20
th
), the (
→
)
display changes to ‘EXIT’. This will return you to the previous menu.