II K 4-55
Overview of Software
ParNo.
Parameter name and significance
Min
Max
Default
Unit
(1)
custom.
setting
Grp 5
Speed Controller
5.01
Speed Ref Sel
Selection of the desired speed reference location:
0 = Macro depend / dependent on the selected
macro
1 = AI1 / analog input 1 (X2:1-2)
2 = AI2 / analog input 2 (X2:3-4)
3 = Bus Main Ref / main fieldbus reference value
4 = Bus Aux Ref / auxiliary fieldbus reference value
5 = Fixed Sp1 / fixed speed value 1 (5.13)
6 = Fixed Sp2 / fixed speed value 2 (5.14)
7 = Commis Ref1 / commissioning ref. value 1
8 = Commis Ref2 / commissioning ref. value 2
9 = Squarewave / square-wave generator
10 = Const Zero / constant zero speed
0
10
0
Text
x
5.02
Wizard
Speed Meas Mode
Selection of the desired speed feedback:
0 = EMF (i.e. without speed measurement)
1 = Analog Tacho
2 = Encoder
0
2
0
Text
x
5.03
Wizard
Encoder Inc
Number of the encoder increments per revolution.
20
10000
1024
integer
x
5.04
Signal
Speed Ref
Actual speed reference value in revolutions/minute.
-
-
-
rpm
5.05
Signal
Speed Act
Actual speed value used by the speed controller, in
revolutions/minute.
-
-
-
rpm
5.06
Signal
Tacho Speed Act
Actual speed value measured by the analog
tachometer, in revolutions/minute.
-
-
-
rpm
5.07
auto-
tuning
Speed Reg KP
Proportional gain of the speed controller
(PI controller).
0.000
19.000
0.200
integer
5.08
auto-
tuning
Speed Reg TI
Integration time constant of the speed controller
(PI controller) in milliseconds.
0.0
6553.5
5000.0
ms
5.09
Wizard
Accel Ramp
Duration of the acceleration ramp in seconds in the
case of acceleration from 0 to maximum speed (1.06).
0.0
3000.0
10.0
s
x
5.10
Wizard
Decel Ramp
Duration of the deceleration ramp in seconds in the
case of deceleration from maximum speed (1.06) to 0.
0.0
3000.0
10.0
s
x
5.11
Wizard
Eme Stop Ramp
Duration of the deceleration ramp in seconds in the
case of deceleration from maximum speed (1.06) to 0,
as a consequence of an emergency stop trip.
0.0
3000.0
10.0
s
x
(1) no changes possible if the drive is in ON-status
Содержание DCS 400
Страница 1: ...II K 1 1 DCS Thyristor power converter for DC drive systems 20 to 1000 A 9 to 522 kW Manual DCS 400 ...
Страница 24: ...II K 3 14 Technical data ...
Страница 29: ...II K 4 5 Overview of Software ...
Страница 158: ...II K 6 36 Operating Instructions ...
Страница 181: ...II K B 1 Appendix B Declaration of conformity ...
Страница 190: ...Notices ...
Страница 191: ...Notices ...