II K 6-10
Operating Instructions
1.06 Max Speed
is set to the value of
1.05 Base Speed
Field weakening Yes/No
Maximum speed for field-
weakening operation
see motor name plate
Selection of desired operat-
ing response at Stop Mode
Acceleration ramp
Deceleration ramp
Selection of desired operat-
ing response at Emergency
stop mode
Deceleration ramp for Emer-
gency Stop Mode
Commissioning step
Comments
No
Fieldweakening?
Yes
OUTPUT
MENU
AUTO OFF HAND REM
LOC
<RUN>
5.09 Accel Ramp
10.0s
OUTPUT
MENU
AUTO OFF HAND REM
LOC
<RUN>
5.10 Decel Ramp
10.0s
OUTPUT
MENU
AUTO OFF HAND REM
LOC
<RUN>
1.06 Max Speed
100rpm
OUTPUT
MENU
AUTO OFF HAND REM
LOC
<RUN>
4.06 Field Low Trip
30%
OUTPUT
MENU
AUTO OFF HAND REM
LOC
<RUN>
Torque Lim
Coast
2.04 Eme Stop Mode
Ramp
OUTPUT
MENU
AUTO OFF HAND REM
LOC
<RUN>
5.11 Eme Stop Ramp
10.0s
OUTPUT
MENU
AUTO OFF HAND REM
LOC
<RUN>
Minimum field current in field
weakening operation
see motor name plate
OUTPUT
MENU
AUTO OFF HAND REM
LOC
<RUN>
Torque Lim
Coast
2.03 Stop Mode
Ramp