II K 7-12
Serial Interfaces
For detailed information please refer to the related
fieldbus adapter description.
In the case you need a fieldbus other than shown,
please contact your local ABB sales office. ABB is
continuously developing on new solutions.
DeviceNet (including parameter transfer)
Parameter
Meaning
Alternative settings
Typical settings
8.01
Module Type
0 = Disable
1 = Fieldbus
2 = RS232-Port
3 = Panel-Port
4 = Res Fieldbus
1 = Fieldbus
8.02
MAC ID
0…63
63
8.03
Baudrate
0 = 125 kBd
1 = 250 kBd
2 = 500 kBd
0 = 125 kBd
8.04
Status
0 = Self Test
1 = No Connect
2 = Connected
3 = Timeout
4 = Dup. Mac. Err.
5 = Bus_Off
6 = Com. Error
7 = Wrong Asmbly
Read only (parameter).
The module shows value ’No
Connect’ after first power-up.
8.05
Profile Selection
0 = ABB Drives
1 = CSA 2.8/3.0
0 = ABB Drives
8.06
Poll Output Select
0 = Basic Speed
3 = Multiple Dataset
8.07
Poll/Cos Input Sel
1 = Transparent
3 = Multiple Dataset
8.08
Cos Data Output
2 = Parameters
3 = Multiple Dataset
3 = Multiple Dataset
8.09
Bit Strobe Output
0 = Basic Speed
1 = Transparent
2 = Parameters
0 = Basic Speed
8.10
DataSet Indexes
0 = FBA DSet 1
1 = FBA DSet 10
0 = FBA DSet 1
8.11
Speed Ref Scale
0…32767
1500
8.12
Speed Act Scale
0…32767
1500
8.13
ABB Drives Stop M.
0 = Coast Stop
1 = Ramp Stop
0 = Coast Stop
8.14
Ramp Stop Level
0…20.000
1000
8.15
No. of Dataset
1…2
2
Table 7.3/1:
Parameter settings for the most commonly used fieldbus adapters
Содержание DCS 400
Страница 1: ...II K 1 1 DCS Thyristor power converter for DC drive systems 20 to 1000 A 9 to 522 kW Manual DCS 400 ...
Страница 24: ...II K 3 14 Technical data ...
Страница 29: ...II K 4 5 Overview of Software ...
Страница 158: ...II K 6 36 Operating Instructions ...
Страница 181: ...II K B 1 Appendix B Declaration of conformity ...
Страница 190: ...Notices ...
Страница 191: ...Notices ...