Isolation areas
The following figure shows the different isolation areas of the module.
41
40
63
62
61
60
Dashed line: reinforced insulation (IEC 61800-5-1).
Connections
■
Motor thermistor connection (60…61)
• Maximum wire size: 1.5 mm
2
(16 AWG)
• Maximum wire length: 700 m (2300 ft) (1400 m [4600 ft] for the
whole loop)
With the specified cable type, detection of a short-circuited PTC
sensor or cable is not guaranteed after 100 m (328 ft).
• Type: Shielded, twisted-pair cable (Draka JAMAK
1×(2+1)×0.5 mm
2
or equivalent)
• Tightening torque: 0.5 N·m (4.4 lbf·in)
Technical data 61