• documentation of start-up activities, references to failure reports
and resolution of failures
• the test results for each safety function, checksums, date of the
tests, and confirmation by the test personnel.
You must store any new validation test reports done due to changes
or maintenance in the logbook of the machine and in the explosion
protection document under the scope of the ATEX User Directive
1999/92/EC or The Dangerous Substances and Explosive
Atmospheres Regulations 2002 (UK).
Start-up
The module is started up through drive parameters. Use the Drive
composer PC tool or the control panel to set the parameter values.
1. Power up the drive.
2. If no warning is shown:
• Make sure that the value of both parameter
15.02 Detected
extension module
and parameter
15.01 Extension module
type
is
CPTC-02
.
If warning A7AB Extension I/O configuration failure is shown:
• Make sure that the value of parameter
15.02 Detected
extension module
is
CPTC-02
• Set parameter
15.01 Extension module type
to
CPTC-02
.
You can now see the parameters of the extension module in
parameter group
15 I/O extension module
. See the firmware manual.
In addition, set the parameters in this table.