3. Install the drive, including the components of the ATEX-certified
motor thermal protection function, outside the potentially explosive
atmosphere.
4. For the sensor connection, ABB recommends to use shielded
twisted-pair cable. This type of cable decreases electromagnetic
interference in the sensor circuit.
5. Route the sensor cables away from the motor cable. Power cables
can cause electromagnetic interference in the sensor circuit.
6. Ground all sensor cable shields to a single grounding point
outside the potentially explosive atmosphere. 360-degree
grounding of the cable shields at the cable entry of the drive is
recommended. Do not connect the cable shields to ground at the
sensor end of the cable.
Terminal designations
■
Motor thermistor connection
Description
Marking
PTC connection
PTC IN
60
Ground (earth) potential
PTC IN
61
■
Relay output connection
Description
Marking
Common, C
RO PTC C
62
Normally open, NO
RO PTC C
63
■
External power supply
The external power supply is needed only if you want to connect an
external back-up power supply for the drive control unit.
Electrical installation 37