from generating the torque required to rotate the motor. If the motor
is running when STO function is activated, it coasts to a stop.
For more information on the drive STO function, see the appropriate
drive hardware manual.
■
Wall-mounted drives and drive modules
The module is available as an add-on kit (L537+Q971). If you
intend to retrofit the CPTC-02 module to an installed drive, you need
to make sure that the ATEX/UKEX certification enables the retrofit.
Contact your local ABB representative for more information.
The user:
• makes sure that the serial number of the drive starts with 1, 4,
7, 8, M or Y,
• pairs the CPTC-02 module with an ATEX/UKEX-certified ACS580,
ACH580 or ACQ580 drive in the ABB Drive Installed Base (DIB)
register,
See
Instructions for pairing the module with an ATEX-certified
drive
(3AXD10001243391 [English]).
• attaches the included ATEX/UKEX label for the SMT function
near the type designation label (CE/UKCA marking) of the drive,
• installs the option module to Option slot 2 of the drive control unit
and sets the applicable drive parameters,
• connects the PTC temperature sensors of the motor to the PTC
input of the option module, and
• connects the drive STO terminals to the relay output of the option
module.
■
Cabinet-installed drives
For cabinet-installed drives, the module is available as a
factory-installed L537+Q971.
28 Option description