13
—
Measurements and Events definition
—
Events
If a measurement object (e.g. TRMS current of a branch) crosses predefined threshold conditions
(value, direction and delay time) then an event is registered.
Following options linked to events logging are available:
• Visualization of all detected events in WebUi
• Reading event/alarm status through Modbus register
• Export via FTP and Email
In order to configure an event, specifications of the following are required:
• The threshold value
• Indication of cross direction (cross up, cross down)
• Indication of delay time
Events can be linked both to mains and branches object values:
Branches
Object
Unit Alarm cross
Resolution Format
Status up/down Threshold
no Alarm
0
Current TRMS
A
11
up
0.01
unsigned
Current TRMS
A
12
down
0.01
unsigned
Active power P
W
41
up
1
unsigned
Active power P
W
42
down
1
unsigned
Mains
Objekt
Unit
Alarm cross
Resolution Format L1 L2 L3 N
Status up/down Threshold
no Alarm
0
x
x
x
x
I
A
11
up
0.01
unsigned
x
x
x
x
I
A
12
down
0.01
unsigned
x
x
x
x
THD-I
%
21
up
0.01
unsigned
x
x
x
x
THD-I
%
22
down
0.01
unsigned
x
x
x
x
U
V
31
up
0.01
unsigned x x x
U
V
32
down
0.01
unsigned x x x
THD-U
%
41
up
0.01
unsigned
x
x
x
THD-U
%
42
down
0.01
unsigned
x
x
x
P
W
51
up
1
singed x x x
P
W
52
down
1
singed x x x
S
VA
61
up
1
unsigned x x x
S
VA
62
down
1
unsigned x x x
Q
var
71
up
1
signed x x x
Q
var
72
down
1
signed x x x
Power factor
-
81
up
0.01
singed
x
x
x
Power factor
-
82
down
0.01
singed
x
x
x
Active Energy
Wh
121
up
10
singed
x
x
x
Active Energy
Wh
122
down
10
singed
x
x
x
The type of event is available on Modbus map as Alarm Status. Resolution refers to the accuracy with
which the value is defined. If several events occur for the same main or branch, the newest one will be
given out via Modbus.
Three register blocks are available in the Modbus register map:
• only object type with alarm code
• object type with alarm code and threshold value
• number of currently active alarms
Содержание CMS-700
Страница 3: ......
Страница 5: ...4 CMS 700 SYSTEM CIRCUIT MONITORING SYSTEM CMS ...