CMS-700 SYSTEM
CIRCUIT MONITORING SYSTEM (CMS)
25
—
Initial Commissioning
—
Network Connection
For the first setup you have to use the direct LAN connection.
Follow instructions under item b. Direct LAN Connection
Check the internal time of the device.
If it is not correct, it has to be set manually.
For further information about manual time setting, settings menu - Other / Time.
The following sections show the steps needed to set up the CMS-700 control unit.
The control unit can be used in different operating modes:
• LAN connection via router
• Direct LAN connection
• Additionally, all data are available through serial port:
- Modbus RTU (RS485)
Static access with default factory setting
Details
1
Access to web user interface with default IP of control unit
192.168.1.200:8000
2
Define static IP address for PC, for example:
Make sure the IP address in the assigned LAN is not used twice.
If it is used twice, an adjustment is required.
192.168.1.5
192.168.1.X (X = 0..255)
3
Subnet Mask
255.255.255.0
4
DHCP access
Note: If you change after initial commissioning for DHCP access
Hostname: CMS-700
5
Download latest software version here:
http://new.abb.com/low-voltage/products/system-pro-m/measurement-
products-for-din-rail/circuit-monitoring-systems