CMS-700 SYSTEM
CIRCUIT MONITORING SYSTEM (CMS)
57
Values with special meanings for calculated branch power and energy values (double word, 32bit)
are reported below:
MIB
To retrieve data from the device using the SNMP object identifier (OID), the MIB files from the
NET-SNMP package should be copied to the correct location on the client station.
The NET-SNMP package can be downloaded from the link:
https://sourceforge.net/projects/net-snmp/files/net-snmp/5.7.3/
In the downloaded zip package, MIB files are available in directory: net-snmp-5.7.3.zip\
net-snmp-5.7.3\mibs\
The objects used in CMS-700 are defined in SNMPv2-MIB.txt and NET-SNMP-EXTEND- MIB.txt.
The list of available objects is shown in Table 1.
All objects are read-only. In case of a NET-SNMP-EXTEND::nsExtendOutputFull object, the var field is
one of variables defined in table Modbus and SNMP Mapping, for example:
NET-SNMP-EXTEND::nsExtendOutputFull."TRMSsens1".
To return all TRMSsens values in a single snmpget request, please use the "TRMSsensAll" variable name.
SNMP Object Identifier
SMI Data Type
SMI Data Type Example Value
SNMPv2-MIB::sysDescr.0
STRING
ABBCircuitMeasurementSy
stemCMS700
SNMPv2-MIB::sysUpTime.0
Timeticks
(117750) 0:19:37.50
SNMPv2-MIB::sysName.0
STRING
CMS700
SNMPv2-MIB::sysLocation.0
STRING
Location of the CMS-700
SNMPv2-MIB::sysServices.0
INTEGER
72
NET-SNMP-EXTEND:nsExtendOutputFull."var"
STRING
12
Special values
Meaning
FFFF 7FF0h
Data pending, acquisition in progress
FFFF 7FF1h … FFFF 7FFBh
Reserved
FFFF 7FFCh
The sensor is known but not accessible at the moment
FFFF 7FFDh
Data type TrueRMS / AC / DC is disabled
FFFF 7FFEh
Overload (beyond full range)
FFFF 7FFFh
Forbidden (no Sensor with ID xx)
—
SNMP objects
—
Simple Network Management Protocol – SNMP