CMS-700 SYSTEM
CIRCUIT MONITORING SYSTEM (CMS)
—
FAQ
Number
Topic
Explanation
1
Current limit mains
power factor
The CMS-700 gathers mains and N phase currents L1, L2, L3 based on the secondary current of the current
transformer starting from a current of 60mA. Below 60mA, the current value is shown as 0A.
For the primary current with a 20/5 current transformer this means: 60mA * 20/5 = 60mA * 4 = 240mA (phase
current). Below a line current of 240mA, the current value is shown as 0A.
If the CMS-700 measures no mains current (= 0A), the power factor is 1.
2
Energy value
Only the accumulated energy value can be read.
In order to obtain values for 15 minutes, the control system (master system) needs to poll data every 15
minutes and then subtract the last value (previous 15 minutes).
3
Max. energy value
The max. energy value for the mains and the individual branches is 429'496 kWh each.
4
Modbus
Modbus values can be read in blocks. The Modbus protocol recognizes the "Read Holding Register" (03h)
function code. This means that the start address (start register) and the number of registers to be issued are
defined (see p. 40 - Read ongoing measurement values of sensor 5-16).
5
Modbus TCP
The RJ45 LAN connection of the device is compatible with Modbus TCP.
6
Master / Slave
The CMS-700 does not have a master function. It operates as a slave and can be addressed accordingly in the
Web UI configuration.
7
Master / Slave
Each CMS-700 needs its own IP address on the network and must be accessed using this IP address.
8
Current direction
There is no current direction detection for AC. For DC measurement, the current direction is detected via
Modbus reading.