CMS-700 SYSTEM
CIRCUIT MONITORING SYSTEM (CMS)
17
System Pro M, SMISSLINE
S800
DIN rail
Cable tie
Mounting method
for all MCBs, RCDs,
RCBOs with
twin terminals
for MCBs
(S200, SMISSLINE) and
RCBOs (SMISSLINE)
for fuse
holders E90
(1000VDC)
for all S800 devices
with cage terminals
universally
usable
universally
usable
Open-core sensors
AC accuracy* of ≤ ± 1.0%
The laying method
influences the accuracy.
18-mm overall width
CMS-120xx (80 A)
CMS-120PS
CMS-120LA
-
CMS-120DR
CMS-120CA
CMS-121xx (40 A)
CMS-121PS
CMS-121LA
CMS-121FH
CMS-121DR
CMS-121CA
CMS-122xx (20 A)
CMS-122PS
CMS-122LA
CMS-122FH
CMS-122DR
CMS-122CA
Solid-core sensors
AC accuracy* of ≤ ± 0.5%
18-mm overall width
CMS-100xx (80 A)
CMS-100PS
CMS-100S8
CMS-100DR
CMS-100CA
CMS-101xx (40 A)
CMS-101PS
CMS-101S8
CMS-101DR
CMS-101CA
CMS-102xx (20 A)
CMS-102PS
CMS-102S8
CMS-102DR
CMS-102CA
25-mm overall width
CMS-200xx (160 A)
CMS-200S8
CMS-200DR
CMS-200CA
CMS-201xx (80 A)
CMS-201S8
CMS-201DR
CMS-201CA
CMS-202xx (40 A)
CMS-202S8
CMS-202DR
CMS-202CA
* All accuracy specifications refer to the relevant full scale value and apply to 25°C
—
Current Transformer
Example: CT PRO XT 250
—
Components of CMS system
—
CMS Flat Cable
The CMS flat cable is a 4-pin cable for connecting multiple sensors to one control unit. The cable
is available in the following four lengths: 2m (CMS-800), 5m (CMS-802), 10m (CMS-803),
and 30m (CMS-805).
Please take into account the following information on the possible cable length of the CMS flat cable
depending on the number and shape of sensors:
Maximum flat cable length in m
Number of sensors
Solid-core sensors
Open-core sensors
32
4.5
7.5
28
5.0
8.5
24
6.0
10.0
20
7.0
12.0
16
8.5
15.0
12
11.0
20.0
8
16.0
30.0
• Do not exceed a total flat cable length of 32m for all CMS-Bus lines for each control unit.
•
Flat cables longer than approx. 15m could require a 120Ω terminating resistor between the two inner
wires at the far end.
• For the flat cable, please consider:
- Use within closed housings only
- Keep a distance of min. 5.5 mm to uninsulated live parts
- Where necessary, additional protection against mechanical stress or UV radiation must be ensured.