Description of application and parameters
Application "RTC"
Product manual 2CKA001473B9679
│97
11.4.16 Basic stage heating - Hysteresis (x 0.1°C)
Options:
Setting option from 3 to 255
The hysteresis of the two-point controller specifies the fluctuation range of the controller around
the setpoint value. The lower switching point is located at "Setpoint value minus switch-on point"
and the upper point is at "Setpoint value plus switch-off point".
Notice
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On" or "2-point 1 Byte, 0/100%".
11.4.17 Basic stage heating - Control value difference for sending of heating control value
Options:
2%
5%
10%
Send cyclic only
The control values of the 0 - 100% PI continuous controller are not transmitted after every new
calculation. Instead, they are transmitted when the calculation results in a value that is different
enough to the previous sent value. This value difference can be entered here.
Notice
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%,"PI PWM, On/Off“ or "Fan coil".
11.4.18 Basic stage heating — Cyclic sending of the control value
Options:
Setting option from 00:01:00 to 01:00:00 (hh:mm:ss)
The current calculated control value used by the device must be cyclically transmitted to the
bus.
Notice
This parameter is only available when the "Control value type" parameter
is set either on "2-point 1 bit, on/off", "2-point 1 byte, 0/100%", "PI continuous, 0-
100%" or "Fan coil".