Description of application and parameters
Application "Function block x"
Product manual 2CKA001473B9679
│273
11.7.17.5
Enable object after return of voltage
Options:
Blocked
Enabled
■
Blocked:
– Object "Sx: enable" is not activated at bus voltage recovery. The blocking function is
deactivated.
■
Enabled:
– If object "Sx: enable" was activated prior to bus voltage recovery, it will also be activated
after bus voltage recovery.
The parameter serves to ensure that a defined value is present on communication object "GF1:
enable" after a return of bus voltage.
Note
This parameter can only be set if the "Enable object" parameter is set on
"activated".
11.7.17.6
Send comfort object
Options:
Deactivated
Activated
■
Deactivated:
– No telegram is sent via object "Sx: comfort operating mode" at the press of the
operating mode switchover button.
■
Activated:
– A telegram is sent via object "Sx: comfort operating mode" at the press of the operating
mode switchover button.
– The telegram that is sent, always has the inverted value of the value sent last. This
means that "0" or "1" is sent (toggle mode) alternately via object "Sx: comfort operating
mode" at each press of the button.
The parameter is used to specify whether a telegram is sent on the bus via the 1-bit
communication object "Sx: comfort operating mode" when the operating mode switchover
button is pressed. This may be necessary for switching the linked room temperature controller
(RTC) into a defined operating mode.
Note
The parameter can only be set if the "Object type for output" parameter is set on
"1 bit" and the "Operating mode" parameter is set on "Comfort", "Standby" or
"ECO".