Communication objects
Communication objects
Product manual 2CKA001473B9679
│350
12.1.47 RTC - Confirm setpoint
Name
Object function
Data type
RTC: Confirm set value (master)
Output
9.001 Temperature value
9.002 Differential temperature value
6.010 Counter value
RTC: Confirm set value (slave)
Input
9.001 Temperature value
9.002 Differential temperature value
6.010 Counter value
The communication object is used to transmit the setpoint confirmation of the master device to a
slave device. The format can be an absolute or relative temperature value or a counter value
which is multiplied with an adjustable step size (standard value 0.5 K). This value the slave
device adopts as starting point for a further setpoint adjustment.
Notice
When the master/slave operation is activated, the object "RTC: Confirm setpoint
(master)" of the master device for synchronisation must be connected with
object "RTC: Confirm setpoint (slave)" of the slave device.
12.1.48 RTC - Heating/cooling request
Name
Object function
Data type
RTC: Heating/cooling request
(Master)
Input
1.100 Heating / Cooling
RTC: Heating/cooling request
(Slave)
Output
1.100 Heating / Cooling
The communication object is used to transmit the heating/cooling switchover request of the
button operation of a slave device to the master device. The confirmation is made via object
"Heating/cooling switchover".
Notice
When the master/slave operation is activated, the object "RTC: Heating/cooling
request (master)" of the master device for synchronisation must be connected
with object "RTC: Heating/cooling request (slave)" of the slave device.