Description of application and parameters
Application "Function block x"
Product manual 2CKA001473B9679
│218
11.7.4.7
Dimming stop telegram
Options:
Dimming stop is not sent
Dimming stop is sent
■
Dimming stop is not sent:
– When the button is released, no "Stop dimming" command is sent.
■
Dimming stop is sent:
– When the button is released, the command "Stop dimming" is sent.
The parameter is used to specify whether the "Stop dimming" command is sent when the button
is released after a long press. Hence, a connected dimming actuator can be halted at any time
during the dimming phase.
Note
This parameter is only adjustable if parameter "Manner of dimming" is set on
"Step-wise dimming" and parameter "Dimming function" is set on "Short
operation switching, long operation dimming".
11.7.4.8
Cyclic sending of the dimming telegrams
Options:
Deactivated
Activated
■
Deactivated:
– No dimming telegrams are sent cyclic as long as the button is pressed.
■
Activated:
– Telegrams are sent cyclic as long as the button is pressed.
The parameter is used to specify whether dimming telegrams are sent cyclic on the bus via 3-bit
communication object "S1: relative dimming" as long as the button is pressed.
After releasing the button, the cyclic sending of the dimming telegrams is stopped. The cycle
time is specified via the "Duration of the telegram repetition" parameter.
Note
This parameter is only adjustable if parameter "Manner of dimming" is set on
"Step-wise dimming" and parameter "Dimming function" is set on "Short
operation switching, long operation dimming".