Description of application and parameters
"Relative humidity" application
Product manual 2CKA001473B9679
│198
11.6.43 Step controller - Value at measurement value failure (scene)
Options:
0-64
If the internal or external measurement malfunctions or fails, a defined value can be sent via this
parameter.
Notice
The parameter is available only when parameter "Control value output format" is
set on "Scene".
11.6.44 PI controller — Setpoint (10…95%RH)
Options:
10-95
The parameter defines which value should be sent after the threshold value is undershot or
when the value is below this threshold value.
Notice
The parameter is available only when parameter "Controller type" is set on "PI".
11.6.45 PI controller - Proportional range (10...40%RH)
Options:
10-40
The parameter defines which value should be sent after the threshold value is exceeded or
when the value is above this threshold value.
Notice
The parameter is available only when parameter "Controller type" is set on "PI".
11.6.46 PI controller — Readjust time (15…240 min)
Options:
15-240
The first basic value from which a reaction should be triggered, e.g., "Fan speed level 1" is
defined via threshold 3.
Notice
The parameter is available only when parameter "Controller type" is set on "PI".