Description of application and parameters
Application "Primary function"
Product manual 2CKA001473B9679
│84
11.2.1.3
Reaction on falling edge
Options:
Value 1
Value 2
Alternating value1/value2
Deactivated
■
Value 1:
– Value 1 is sent when the button is released (at falling edge).
■
Value 2:
– Value 2 is sent when the button is released (at falling edge).
■
Alternating value 1/value 2:
– Value 1 and value 2 are sent alternately when the button is released.
■
Deactivated:
– No telegram is sent when the button is released.
Application "1-button value switching" can differentiate between the press and the releasing of a
button. A press is defined as "Rising edge" and the releasing as "Falling edge".
The parameter is used to specify whether a telegram with value 1 or value 2 is sent on the bus
at a falling edge via communication object "PF: switching". A further option can be specified as
to whether the telegrams are sent alternately. This means that after value 1 has been sent,
value 2 is sent at a renewed release of the button. After it is released again, value 1 is again
sent out.
Note
Parameter "Value 1" and "Value 2" is used to specify the values that are to be
sent.
11.2.1.4
Consider device enable
Options:
Deactivated
Activated
■
Deactivated:
– Device enable is not taken into account for the primary function.
■
Activated:
– Device enable is taken into account for the primary function.
The primary function can be included in the device enable via the parameter. The parameter
must be activated for this. Operating the device via the primary would then not be possible in a
disabled state.
When the parameter is deactivated the device enable or blockage has an effect only on the
individual buttons.