Planning the electrical installation
84
Implementing the Prevention of unexpected start function
The drive equipped with Q950 supports the Prevention of unexpected start
function according to standards IEC/EN 60204-1:1997; ISO/DIS 14118:1996 and
EN 1037:1996. The circuit conforms to EN 954-1, Category 3.
The Prevention of unexpected start function disables the control voltage of the
power semiconductors of the drive output stage, thus preventing the motor-side
converter from generating the voltage required to rotate the motor. By using this
function, short-time operations (like cleaning) and/or maintenance work on non-
electrical parts of the machinery can be performed without switching off the power
supply to the drive.
The operator activates the prevention of unexpected start function using a switch
mounted on a control desk. When the function is activated, the switch is opened, and
an indicator lamp will light.
WARNING!
The prevention of unexpected start function does not disconnect the
voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
on electrical parts of the drive can only be carried out after isolating the drive system
from the main supply.
Note:
If a running drive is stopped by using the Prevention of unexpected start
function, the drive will cut off the motor supply voltage and the motor will coast to
stop.
For more information, see
Wiring, start-up and operation instructions of safety
options (+Q950, +Q951, +Q952, +Q963, +Q964, +Q967 and +Q968) for ACS800
cabinet-installed drives
(3AUA0000026238 [English]).
Содержание ACS800-17LC
Страница 1: ...ABB industrial drives Hardware manual ACS800 17LC Drives 55 to 5200 kW ...
Страница 4: ......
Страница 10: ...Update notice 6 ...
Страница 18: ...Table of contents 12 ...
Страница 26: ...Safety instructions 20 ...
Страница 32: ...Introduction to the manual 26 ...
Страница 60: ...Hardware description 54 ...
Страница 74: ...Mechanical installation 68 ...
Страница 114: ...Electrical installation 108 ...
Страница 142: ...Maintenance 136 ...
Страница 150: ...Internal cooling circuit 144 ...
Страница 179: ...Dimensions 173 Frame sizes R7i R7i and R8i R8i bottom entry exit ...
Страница 180: ...Dimensions 174 Frame sizes R7i R7i and R8i R8i marine units C121 ...
Страница 182: ...www abb com drives www abb com drivespartners Contact us 3AUA0000065339 Rev B EN 2016 06 07 ...