Mechanical installation
60
Fastening the cabinet to the floor and wall (non-marine units)
Fasten the cabinet to the floor by using clamps along the edge of the cabinet bottom,
or by bolting the cabinet to the floor through the holes inside.
Alternative 1 – Clamping
Insert the clamps into the twin slots along the front and rear edges of the cabinet
frame body and fasten them to the floor with a bolt. The recommended maximum
distance between the clamps is 800 mm (31.5”).
If there is not enough working space behind the cabinet for mounting, replace the
lifting bars at the top with L-brackets (not included) and fasten the top of the cabinet
to the wall.
Clamp dimensions in millimetres
Cabinet frame
Distances between slots
Cubicle
Width
(mm)
Distance in millimetres and (inches)
300
150 (5.9”)
400
250 (9.85”)
500
350 (13.78”)
600
450 (17.72”)
700
550 (21.65”)
800
650 (25.6”)
Cabinet frame
Fastening the cabinet at the top when floor mounting
from back is not possible (side view)
L-bracket
M16 screw
Cabinet top
Slot detail, front view (dimensions in
millimetres)
Side view
View from above
Содержание ACS800-17LC
Страница 1: ...ABB industrial drives Hardware manual ACS800 17LC Drives 55 to 5200 kW ...
Страница 4: ......
Страница 10: ...Update notice 6 ...
Страница 18: ...Table of contents 12 ...
Страница 26: ...Safety instructions 20 ...
Страница 32: ...Introduction to the manual 26 ...
Страница 60: ...Hardware description 54 ...
Страница 74: ...Mechanical installation 68 ...
Страница 114: ...Electrical installation 108 ...
Страница 142: ...Maintenance 136 ...
Страница 150: ...Internal cooling circuit 144 ...
Страница 179: ...Dimensions 173 Frame sizes R7i R7i and R8i R8i bottom entry exit ...
Страница 180: ...Dimensions 174 Frame sizes R7i R7i and R8i R8i marine units C121 ...
Страница 182: ...www abb com drives www abb com drivespartners Contact us 3AUA0000065339 Rev B EN 2016 06 07 ...