60 Guidelines for planning the electrical installation
Implementing the Power-loss ride-through function
Implement the power-loss ride-through function as follows:
•
Check that the power-loss ride-through function of the drive is enabled with parameter
30.31 Undervoltage control
.
•
Set parameter
21.01 Vector start mode
to
Automatic
(in vector mode) or parameter
21.19 Scalar start mode
to
Automatic
(in scalar mode) to make flying start (starting
into a rotating motor) possible. If the installation is equipped with a main contactor,
prevent its tripping at the input power break. For example, use a time delay relay
(hold) in the contactor control circuit.
WARNING!
Make sure that the flying restart of the motor will not cause any
danger. If you are in doubt, do not implement the Power-loss ride-through
function.
Units with line contactor (F250)
The main contactor of the drive opens in a power-loss situation. When the power returns,
the contactor closes. However, if the power-loss situation lasts so long that the drive trips
on undervoltage, it must be reset and started again to continue operation. If the power-loss
situation lasts so long that the buffering module (C22) empties, the main contactor remains
open and the drive operates only after reset
and a new start.
Supplying power for the auxiliary circuits
The drive is equipped with an auxiliary control voltage transformer which supplies control
voltage, for example, for the control devices and cabinet fan(s).
The following options are to be supplied from external power sources:
•
+G300 Cabinet heaters and/or lighting (230 or 115 V AC; external fuse: 16 A gG).
Using power factor compensation capacitors with the
drive
Power factor compensation is not needed with AC drives.
WARNING!
Do not connect power factor compensation capacitors or harmonic
filters to the motor cables (between the drive and the motor). They are not meant
to be used with AC drives and can cause permanent damage to the drive or
themselves.
Implementing a safety switch between the drive and the
motor
ABB recommends to install a safety switch between the permanent magnet synchronous
motor and the drive output. The switch is needed to isolate the motor during any
maintenance work on the drive.
Содержание ACS580-07-0495A-4
Страница 1: ...ABB general purpose drives Hardware manual ACS580 07 drives 250 to 500 kW ...
Страница 4: ......
Страница 8: ...4 Update notice ...
Страница 16: ...12 ...
Страница 24: ...20 Safety instructions ...
Страница 42: ...38 Operation principle and hardware description ...
Страница 74: ...70 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Страница 82: ...78 Electrical installation ...
Страница 102: ...98 Fault tracing ...
Страница 114: ...110 Maintenance R10 and R11 4 5 2 7 6 3 8 ...
Страница 115: ...Maintenance 111 R10 and R11 9 10 ...
Страница 116: ...112 Maintenance R10 and R11 11 ...
Страница 117: ...Maintenance 113 R10 and R11 12b 12a ...
Страница 118: ...114 Maintenance R10 and R11 R10 and R11 17 14 13 R11 15 16 ...
Страница 126: ...122 Technical data Input and motor cable terminal dimensions of frame R10 Bottom entry and exit ...
Страница 127: ...Technical data 123 Input and motor cable terminal dimensions of frame R11 Bottom entry and exit ...
Страница 134: ...130 Technical data ...
Страница 137: ...Dimension drawings 133 13 Dimension drawings Example dimension drawings are shown below ...
Страница 138: ...134 Dimension drawings Frames R10 and R11 IP42 ...
Страница 139: ...Dimension drawings 135 Frames R10 and R11 IP54 option B055 ...
Страница 140: ...136 Dimension drawings ...
Страница 152: ...148 Safe torque off function ...
Страница 174: ...Contact us www abb com drives www abb com drivespartners 3AXD50000032622 Rev A EN 2016 03 16 ...