144 Safe torque off function
Use
1. Open the activation switch, or activate the safety functionality that is wired to the STO
connection.
2. STO inputs on the drive control unit de-energize, and the drive control unit cuts off the
control voltage from the inverter IGBTs.
3. The control program generates an indication as defined by parameter 31.22 (refer to
the firmware manual of the drive).
4. Motor coasts to stop (if running). The drive will not restart while the activation switch or
safety relay contacts are open.
5. Deactivate the STO by closing the activation switch, or reseting the safety functionality
that is wired to the STO connection.
6. Reset any faults before restarting.
WARNING!
The Safe torque off function does not disconnect the voltage of the
main and auxiliary circuits from the drive. Therefore maintenance work on
electrical parts of the drive or the motor can only be carried out after isolating the
drive system from the main supply.
WARNING!
(With permanent magnet or synchronous reluctance [SynRM] motors
only) In case of a multiple IGBT power semiconductor failure, the drive system
can produce an alignment torque which maximally rotates the motor shaft by
180/
p
(with permanent magnet motors) or 180/2
p
(with synchronous reluctance [SynRM]
motors) degrees regardless of the activation of the Safe torque off function.
p
denotes the
Close the disconnector and switch the power on.
Test the operation of the STO function when the motor is stopped.
• Give a stop command for the drive (if running) and wait until the motor shaft is at a standstill.
Make sure that the drive operates as follows:
• Open the STO circuit. The drive generates an indication if one is defined for ‘stopped’ state in
parameter 31.22 (see the firmware manual).
• Give a start command to verify that the STO function blocks the drive operations. The motor should
not start.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the STO function when the motor is running:
• Start the drive and make sure the motor is running.
• Open the STO circuit. The motor should stop. The drive generates an indication if one is defined for
‘running’ state in parameter 31.22 (see the firmware manual).
• Reset any active faults and try to start the drive.
• Make sure that the motor stays at standstill and the drive operates as described above in testing
the operation when the motor is stopped.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
Document and sign the acceptance test report which verifies that the safety function is safe and
accepted for operation.
Action
Содержание ACS580-07-0495A-4
Страница 1: ...ABB general purpose drives Hardware manual ACS580 07 drives 250 to 500 kW ...
Страница 4: ......
Страница 8: ...4 Update notice ...
Страница 16: ...12 ...
Страница 24: ...20 Safety instructions ...
Страница 42: ...38 Operation principle and hardware description ...
Страница 74: ...70 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Страница 82: ...78 Electrical installation ...
Страница 102: ...98 Fault tracing ...
Страница 114: ...110 Maintenance R10 and R11 4 5 2 7 6 3 8 ...
Страница 115: ...Maintenance 111 R10 and R11 9 10 ...
Страница 116: ...112 Maintenance R10 and R11 11 ...
Страница 117: ...Maintenance 113 R10 and R11 12b 12a ...
Страница 118: ...114 Maintenance R10 and R11 R10 and R11 17 14 13 R11 15 16 ...
Страница 126: ...122 Technical data Input and motor cable terminal dimensions of frame R10 Bottom entry and exit ...
Страница 127: ...Technical data 123 Input and motor cable terminal dimensions of frame R11 Bottom entry and exit ...
Страница 134: ...130 Technical data ...
Страница 137: ...Dimension drawings 133 13 Dimension drawings Example dimension drawings are shown below ...
Страница 138: ...134 Dimension drawings Frames R10 and R11 IP42 ...
Страница 139: ...Dimension drawings 135 Frames R10 and R11 IP54 option B055 ...
Страница 140: ...136 Dimension drawings ...
Страница 152: ...148 Safe torque off function ...
Страница 174: ...Contact us www abb com drives www abb com drivespartners 3AXD50000032622 Rev A EN 2016 03 16 ...