Operation principle and hardware description 33
Degree of protection
Definitions
According to IEC/EN 60529, the degree of protection is indicated by an IP code where the
first numeral means protection against ingress of solid foreign objects, and the second
numeral protection against ingress of water. The IP codes of the standard cabinet and
options covered in this manual are defined below.
IP42 and UL Type 1 Filtered (standard)
The air inlet gratings are covered with a metallic mesh between the inner metallic grating
and the outer plastic grating.
IP54 and UL Type 12 (B055)
This option provides the degree of protection of IP54 (UL type 12). It equips the cabinet air
inlets with filter housings containing folded board air filter mats between the inner metallic
grating and the outer plastic grating. An additional fan on the cabinet roof is included.
Empty cubicles (oC196 to +C201)
These options provide an empty cubicle to the drive cabinet:
•
on the right-hand side of the converter cubicle (400 mm wide with C196,
600 mm wide with C197 and 800 mm wide with C198)
•
on the left-hand side of the converter cubicle (400 mm wide with C199,
600 mm wide with C200 and 800 mm wide with C201).
du/dt filter (E205)
The du/dt filter protects the motor insulating system by reducing the voltage rise speed at
the motor terminals. The filter also protects the motor bearings by reducing the bearing
currents.
More information on when the option is required: See section
Examining the compatibility
of the motor and drive
on page
.
Cabinet heater with external supply (G300)
The option contains:
•
50 W heating elements in the cubicles where needed
•
load switch for providing electrical isolation during service
•
miniature circuit breaker for overcurrent protection
•
terminal block for external power supply.
The heater prevents humidity condensation inside the cabinet when the drive is not
running. The power output of the semiconductor-type heating elements depends on the
environmental temperature. The customer must switch the heating off when it is not
needed by cutting the supply voltage off.
The customer must supply the heater from an external 110…240 V AC power source.
IP code
The equipment is protected …
First numeral
Second numeral
IP42
against ingress of solid foreign objects > 1 mm
against dripping (15° tilting) water
IP54
dust-protected
against splashing water
Содержание ACS580-07-0495A-4
Страница 1: ...ABB general purpose drives Hardware manual ACS580 07 drives 250 to 500 kW ...
Страница 4: ......
Страница 8: ...4 Update notice ...
Страница 16: ...12 ...
Страница 24: ...20 Safety instructions ...
Страница 42: ...38 Operation principle and hardware description ...
Страница 74: ...70 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Страница 82: ...78 Electrical installation ...
Страница 102: ...98 Fault tracing ...
Страница 114: ...110 Maintenance R10 and R11 4 5 2 7 6 3 8 ...
Страница 115: ...Maintenance 111 R10 and R11 9 10 ...
Страница 116: ...112 Maintenance R10 and R11 11 ...
Страница 117: ...Maintenance 113 R10 and R11 12b 12a ...
Страница 118: ...114 Maintenance R10 and R11 R10 and R11 17 14 13 R11 15 16 ...
Страница 126: ...122 Technical data Input and motor cable terminal dimensions of frame R10 Bottom entry and exit ...
Страница 127: ...Technical data 123 Input and motor cable terminal dimensions of frame R11 Bottom entry and exit ...
Страница 134: ...130 Technical data ...
Страница 137: ...Dimension drawings 133 13 Dimension drawings Example dimension drawings are shown below ...
Страница 138: ...134 Dimension drawings Frames R10 and R11 IP42 ...
Страница 139: ...Dimension drawings 135 Frames R10 and R11 IP54 option B055 ...
Страница 140: ...136 Dimension drawings ...
Страница 152: ...148 Safe torque off function ...
Страница 174: ...Contact us www abb com drives www abb com drivespartners 3AXD50000032622 Rev A EN 2016 03 16 ...