03 POWER ELECTRONICS AND CABINET FEATURES
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
41/174
3.4.6
Grounding switch
The grounding switch is a safety device that enables safe access to the medium voltage
compartments of the drive.
The drive is equipped with one of the following switchgear:
- Grounding switch (1 in Fig. 3-9)
- Combined input disconnector and grounding switch (2 in Fig. 3-9)
The input disconnector and the grounding switch are mechanically coupled and operated with
a single lever.
Figure 3-9: Switchgear of the drive
The switch is electro-mechanically interlocked with a discharge monitoring circuit that
prevents turning of the switch while the DC-link capacitors are still charged. When the drive is
grounded, the DC link of the drive is connected to the PE ground busbar.
(1) Grounding switch
(2) Combined input disconnector and
grounding switch
1
2
Содержание ACS1000i air-cooled
Страница 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000i air cooled User manual ...
Страница 3: ...Contents ACS1000i air cooled User manual ...
Страница 5: ... 01 About this manual 01 5 16 ...
Страница 16: ......
Страница 17: ... 02 Important safety information 02 17 28 ...
Страница 28: ......
Страница 29: ... 03 Power electronics and cabinet features03 29 56 ...
Страница 57: ... 04 Control system 04 57 70 ...
Страница 71: ... 05 Transportation storage and disposal05 71 78 ...
Страница 78: ......
Страница 79: ... 06 Mechanical installation 06 79 88 ...
Страница 88: ......
Страница 89: ... 07 Electrical installation07 89 104 ...
Страница 105: ... 08 Commissioning 08 105 110 ...
Страница 110: ......
Страница 111: ... 09 Operation 09 111 124 ...
Страница 125: ... 10 CDP control panel 10 125 148 ...
Страница 149: ... 11 Preventive and corrective maintenance 11 149 172 ...
Страница 173: ......