11 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
161/174
4. Rack-out, lock-out, ground and tag-out the main power feeder.
5. If the grounding switch is equipped with the optional lock (1) that secures the switch in the
ungrounded position, unlock the grounding switch.
6. Wait until the yellow lamp GROUNDING SWITCH UNLOCKED lights up.
The lamp lights up when cooling stops after a delay time.
- If the yellow lamp is on, continue with “11.6.3 Grounding” on page 162.
- If the yellow lamp is not on, continue with “11.6.4 Grounding switch is not released”
1