09 OPERATION
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
121/174
5. Start the motor.
- After the motor has been magnetized, the motor speed ramps up to the reference value.
- While the motor is accelerating, the run status indication on the display blinks. When the
motor speed has reached the reference value, the run status indication lights
up permanently.
The display shows
Running
to indicate that the drive is operating.
1 L ->
[600.0 rpm] 0
Status
Ready to Strt
MotorSpeed 0.00 rpm
Power
0.0 %
LOC
RESET
REF
REM
1 L ->
[600.0 rpm] 0
Status
Magnetizing
MotorSpeed 0.00 rpm
Power
0.0 %
1 L ->
600.0 rpm I
Status
Running
MotorSpeed 600.0 rpm
Power
30.0 %
Содержание ACS1000i air-cooled
Страница 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000i air cooled User manual ...
Страница 3: ...Contents ACS1000i air cooled User manual ...
Страница 5: ... 01 About this manual 01 5 16 ...
Страница 16: ......
Страница 17: ... 02 Important safety information 02 17 28 ...
Страница 28: ......
Страница 29: ... 03 Power electronics and cabinet features03 29 56 ...
Страница 57: ... 04 Control system 04 57 70 ...
Страница 71: ... 05 Transportation storage and disposal05 71 78 ...
Страница 78: ......
Страница 79: ... 06 Mechanical installation 06 79 88 ...
Страница 88: ......
Страница 89: ... 07 Electrical installation07 89 104 ...
Страница 105: ... 08 Commissioning 08 105 110 ...
Страница 110: ......
Страница 111: ... 09 Operation 09 111 124 ...
Страница 125: ... 10 CDP control panel 10 125 148 ...
Страница 149: ... 11 Preventive and corrective maintenance 11 149 172 ...
Страница 173: ......